Sanyo Air Conditioner 07AHX52 User Guide

Print Form  
ECO-i Submittal Data  
07AHX52  
Indoor Unit: 1 Way Air Discharge  
Job Name:  
Location:  
Approval:  
Date:  
Engineer:  
Construction:  
Unit #:  
Drawing #:  
Submitted to:  
Submitted by:  
Reference:  
Parts Warranty: 1 Year  
Built in Drain Pump  
Washable Filter  
Wired, Wireless or Simple Remote Option  
Remote Sensor Option  
Capacities  
Fan  
Cooling: Btu/h  
Heating: Btu/h  
Sensible Heat Ratio  
7,500  
8,500  
0.74  
Quantity/Type:  
Fan Motor Output (W):  
Drive:  
Centrifugal  
60  
Direct  
Airflow Rate (L/M/H):  
212 / 247 / 282  
Cooling Mode Nominal Conditions  
Indoor: °F DB/°F WB  
Outdoor: °F DB  
80/67  
95  
Power Supply  
V/PH/Hz.  
208 / 230 / 1 / 60  
25  
0
Pipe Length (feet):  
Level Difference (feet):  
Minimum circuit Amps (MCA): Amps  
Max. Overcurrent Protection (MOCP):  
Nominal Power Input-Cooling (W):  
Nominal Power Input-Heat (W):  
Running Amps:  
15  
15  
48/50  
Heating Mode Nominal Conditions  
Indoor: °F DB  
Outdoor: °F DB/ °F WB  
Pipe Length (feet):  
44/46  
70  
47/43  
25  
0.26/0.29  
43  
Weight (lbs):  
Level Difference (feet):  
0
Sound Data  
Refrigerant and Piping  
Refrigerant Type:  
Metering Device (Electronic Expansion Valve):  
Liquid Piping (inches):  
Sound Level (H/M/L) 5’ below unit:  
33 / 31 / 29  
410A  
EEV  
1/4  
Coil  
1.14  
3
Gas Piping (inches):  
1/2  
Coil Face Area (sq. ft.):  
Number of Rows:  
Condensate  
Drain Piping (OD) Inches:  
1.25  
 

Radio Shack Telephone Desktop Phone User Guide
Renesas Planer 2SC4308 User Guide
Rikaline GPS Receiver CF GPS Receiver User Guide
Rival Fryer CZF530 User Guide
Ryobi Lawn Mower 136 User Guide
Samsung Car Video System HD948 XSS User Guide
Samsung CRT Television CRT Rear Projection TV User Guide
Sanus Systems TV Video Accessories WFV66 User Guide
Sanyo GPS Receiver NVM 4370 User Guide
SATO Printer Accessories GL408e User Guide